Working Principle.
This series reducing valve is pilot piston type reducing valve, mainly composed of main valve and pilot valve. The main valve consists of valve seat, main valve disc, piston, cylinder sleeve, and spring. The piston valve consists of valve seat, valve flap, membrane, spring and adjusting spring. Set the outlet pressure through adjusting spring, sense the change of pressure of outlet with membrane, adjust the flow area of throttling part of main valve through open and close of pilot valve and drive the piston, to realize the function of reducing and regulating valve.Field of Application.
Product Name: RP-6 High-Sensitivity Steam Pressure Reducing Valve.Material of Main Component.
Name Of Component | Material Of Component |
Valve Body,Valve Cover,Seat Cover | WCB |
Valve Seat, Valve Flap | 2Cr13 |
Cylinder Sleeve, Piston | Ampco |
Membrane | PH15-7Mo |
Piston Ring | Polyphenyl |
Pilot Valve Seat, Pilot Valve Rod | 2Cr13 |
Spring Of Main Valve | 50CrVA |
Main Spring Of Pilot Valve | 50CrVA |
Adjusting Spring | 60Si2Mn |
DN | External Dimension | ||
L | H | H1 | |
15 | 140 | 160 | 65 |
20 | 140 | 160 | 65 |
25 | 150 | 168 | 68 |
32 | 180 | 185 | 75 |
40 | 180 | 185 | 78 |
50 | 200 | 193 | 88 |
65 | 230 | 208 | 98 |
80 | 260 | 228 | 117 |
Nominal Pressure | 1.0 Mpa | 1.6 Mpa |
Tested Pressure Of Shell | 1.5 Mpa | 2.4 Mpa |
Sealing Test Pressure | 1.0 Mpa | 1.6 Mpa |
Maximum Upstream Pressure | 1.0 Mpa | 1.6 Mpa |
Pressure Range Of Outlet | 0.04-0.6 Mpa | 0.04-1.0 Mpa |
Minimum Differential Pressure | 0.05 Mpa | 0.04 Mpa |
Medium | Steam | |
Operating Temperature | 425 |
DN | 15 | 20 | 25 | 32 | 40 | 50 | 65 | 80 |
Cv | 1 | 2.5 | 4 | 6.5 | 9 | 16 | 25 | 36 |