Customization: | Available |
---|---|
Certification: | ISO |
Pressure: | High Pressure |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Installation
The preferred installation is in the horizontal position as close as possible to equipment being drained. Install strainer (20 mesh) upstream and full port isolating valves upstream and downstream of trap. Piping to and from the trap should be at least equal to or one
size larger than trap connection. Do not weld pipe connection to trap. Body material is not suitable for welding.
For freeze resistant installations, all drains must be pitched toward the trap for gravity flow. Trap must be installed vertically, discharging downward. Discharge piping must be self-draining.
Material
Serial Number | Parts | Material | |
1 | valve body | Stainless steel | AlSI420 F |
2 | Valve cap | Stainless steel | AlSI 416 |
3 | Disc | Stainless steel | BS1449420 S45 |
4 | Insulation cover | Aluminium | BS1470 SIC M |
Our Services
Pre-sale service:
1.We have full stock and can deliver within short time.
2.OEM and ODM order are accepted, Any kind of logo printing or design are available.
3.Good Quality + Factory Price + Quick Response + Reliable Service, is what we are trying best to offer you.
4.All of our products are produced by our professional workman and we have our high-work-effect foreign trade team, you can totally believe our service.
After you choose:
1. We will count cheapest shipping cost and make invoice to you at once.
2. Check quality again, then send out to you at 1-2 working day after your payment
3. Email you the tracking no., and help to chase the parcels until it arrive you.
After-sale service:
1.We are very glad that customers give us some suggestion for price and products.
2.If you have any question,please contact us freely by E-mail or Telephone.